Reading Ex / ATEX Markings
Zones, gas groups and temperature classes for actuator accessories in hazardous areas.
Updated
- ATEX
- IECEx
- zones
- T-class
Solenoids, switchboxes and positioners on automated valves often sit in hazardous areas. The Ex marking tells you where they can be used.
| Zone (gas) | Explosive atmosphere present |
|---|---|
| Zone 0 | Continuously or for long periods |
| Zone 1 | Likely in normal operation |
| Zone 2 | Not likely, and only briefly if it does |
| T-class | Max component temp during operation (°C) |
|---|---|
| T1 | 450 |
| T2 | 300 |
| T3 | 200 |
| T4 | 135 |
| T5 | 100 |
| T6 | 85 |
Gas groups run IIA (e.g. propane), IIB (e.g. ethylene) to IIC (hydrogen, acetylene). Equipment rated IIC is suitable for IIB and IIA; the reverse is not true.