Skip to content
Vectis Controls

Designing for Ultra-Fast Stroke Times

Where stroke time is really lost, and the components that get it back.

Updated

  • stroke time
  • quick exhaust
  • booster
  • ESD

Stroke time is dominated by how fast you can move fluid, not by actuator size. For a spring-return valve closing on ESD, the limiting factor is almost always the exhaust path from the cylinder.

Where time is lost

  • Small solenoid Cv on the exhaust path
  • Long or small-bore tubing between solenoid and cylinder
  • Restrictive silencers and breathers
  • Over-sized cylinders with a large swept volume
  • Hydraulic return lines with high back-pressure

How to get it back

ComponentEffect
Quick exhaust valveDumps cylinder air locally, bypassing the solenoid and tubing
Volume boosterAmplifies a small pilot signal into high-flow supply/exhaust
Large-bore tubingReduces line losses, particularly on long runs
Hydraulic dump valveRapid release of hydraulic pressure on spring-return hydraulic units
End-of-stroke dampingProtects the valve and actuator from impact at high speed

A frequently quoted rule of thumb for ESD valves is around one second per inch of nominal bore, but the governing requirement is always the process safety time set out in the safety requirements specification. See ESD vs HIPPS vs SSIV.

Connected articles